PMAC802 220V DC Circuit Breaker

FOB Reference Price:Get Latest Price
$0.0001 / Piece | 2 Piece/Pieces (Min. Order)
Shipping:
Support Sea freight
Report Suspicious Activity
Overview
Quick Details
Place of Origin:
Guangdong, China
Brand Name:
PILOT
Model Number:
PMAC802
Type:
Motor controller
Poles Number:
Other
Certificate:
CE
Power supply:
85~265VAC, 80~300VDC
Digital input:
8 channels, external power supply
Relay output:
4 relays, 3NO, 1NC
Capacity of control relay output:
250VAC/10A or 30VDC/ 5A
Communication 1:
RS485/ Modbus
Communication 2:
Profibus DP
Install (main module):
35mm DIN rail
Install ( display unit):
96.5x54.5mm panel mounting
Standard:
IEC61000-4
Supply Ability
Supply Ability:
3000 Set/Sets per Month
Packaging & Delivery
Packaging Details
4 sets/ carton
Port
Zhuhai
Lead Time :
7 days

PMAC802 220V DC Circuit Breaker Features:

 

1. Use module framework. Several modules can be selected flexibly.

 

 2. PMAC802 provides 12 protection functions such as start overtime protection, overload protection, overcurrent protection, phase failure protection, current unbalance protection, earth fault/leakage current protection, short circuit protection, underload protection, external fault protection, overvoltage protection, undervoltage protection, under power protection, phase sequence error protection, EEx e overload protection, temperature (PTC/NTC) protection, analog input protection.

 

 3. Provides measurements of three phases current, three phase /phase voltage, zero phase sequence current, active power, reactive power, power factor, frequency, and active energy measurements.

 

 4. Provides protection, direct starter, reversing direct starter, star/delta starter, and autotransformer starter etc motor starting control modes.

 

 5. Main module provides 9 DIs for start, stop and reset etc. signals input. If more DIs are needed, an extended digital module can be selected. Some of the DIs are programmable.

 

6. Main module provides 5 DOs to meet varies of starting control modes and protection action. If more DOs are needed, an extended digital module can be selected. Some of the DOs are programmable.

 

7. Provides 4~20mA analog output for DCS.

 

8. Through an extended analog module, 2 analog input or 1 analog and 1 hot resistance input can be added.

 

9. Small size and compact configuration.

 

10. Easy installation. Proper for 35mm DIN rail.

 

 

1. Protection:

ProtectionPMAC802PMAC801
start overtime
Over load √ √
Over current √ √
Phase failure √ √
Current unbalance √ √
Short circuit √ √
Earth fault √ √
Under load √ √
External fault √ √
Leakage current optional optional 
Temperture ( PTC/ NTC)  optional
Over voltage optional optional
Under voltage optional  optional
Under power  optional
Phase sequence error   optional
EEx e overload (tE) optonal optional
Analog input  optioanl

 

 

2. Measurement:

ParametersPMAC802    PMAC801    
3 phase current, neutral current, unbalance rate
3 phase voltageoptionaloptional
active / reactive poweroptionaloptional
leakage currentoptionaloptional
power factoroptionaloptional
 frequencyoptionaloptional
active energy (kwh)optionaloptional

 

 

  

You May Like